T2 Garage Exhaust Fans a9e ~.~~~ <br />y 3-4-5 C P <br />3 ron Courts - EF- <br />~ <br />~ <br />~ From: Byron Courts <br />\ To: Oliver Raab <br />~9 Date: Wed, Jun 9, 1999 9:43 AM <br />Subject: EF- 3-4-5 CT2 Garage Exhaust Fans <br />Please check the BHP and FLA of the three motors and compare it to the 20-20-15 MHP shown on the M8.1 equipment schedule. <br />I would like to make sure that we are within the service factor of the motors with the cfm / TSP / MHP that you have indicated . <br />Please let me know what % of FLA and BHP we will be running. <br />Also is there a ciear description of the control sequence for the garage exhaust fans ? <br />CC: Bob Mccune; Craig Lewis; Leonard Lodder <br />