Laserfiche WebLink
North Marion Middle School BO # 99-07141100 <br />OSFM Review Check <br /> <br />(continued on next page) <br /> <br />1) Provide spacing of visual appliances within rooms using the appropriate spacing, candela <br /> ratings and number of appliances in accordance with section 6-4.4.1 of UFC Std. 10-2. <br /> Where NFPA 72-1996, par. 6-4.4.1 is used for location of visual appliances, including <br /> minimum spacing or synchronization for more than two visual appliances within a room, the <br /> requirements of this paragraph ofUFC Std 10-2 will be considered as met. Computer Lab <br /> may require relocation or additional alarm to prevent interruption of field of view of <br /> surrounding area illumination by visual signal. (Sheet E3.40 rooms in general) <br /> <br />2) CONTACT DEPUTY JASON CANE (503)-373-1540 X250) TO SCHEDULE A FINAL <br /> INSPECTION OF THE ABOVE ALARM SYSTEM. <br /> <br />Jason Cane, Deputy State Fire Marshal 2 <br />Office Of State Fire Marshal <br />4760 Portland Rd. NE, Salem, OR. 97305-1760 <br />(503)373-1540 x250 <br />7/14/99 <br /> <br />Working Smoke Detectors Save Lives <br /> <br /> <br />