Laserfiche WebLink
Terry Bonn <br /> <br />September 20, 1998 <br /> <br />Re: Carroll sunroom <br /> <br />The walls (12" x 86") on each side of the double doors and adjacent windows may be considered <br />to be a vertical cantilever beam if plywood is attached to each side. The studs (double on each <br />side) inside this wall may be trimmed to 5" width so that the wall is still 6" width when a layer of <br />15/32 plywood is attached to each side. 8d nails at 3" spacing are needed all around the beam. <br />The vertical studs on the windward side of each of these walls must be anchored with at least a <br />7/8 "diameter bolt. Calculations are attached. <br /> <br />Raymond Kaser <br />1301 Pine <br />Silverton, OR 97381 <br />873-8106 <br /> <br />SEP 2 4 1998 <br /> <br />MARION COUNTY <br />BUILDING INSPECTION <br /> <br /> <br />