Laserfiche WebLink
PAGE 1 December 16, 2013 <br /> PLUMBING FIXTURE ANALYSIS <br /> GERVAIS MIDDLE SCHOOL PHYSICAL EDUCATION EXERCISE ROOM <br /> GERVAIS SCHOOL DISTRICT 1 <br /> RSS ARCHITECTURE, P.C. <br /> ARCHITECT'S PROJECT NO. 1314 <br /> 1. OSSC CHAPTER 29 -TABLE 29-A MINIMUM PLUMBING FIXTURES <br /> Occupancy Group: E <br /> Occupancy Load Factor: 50 S.F. /occupant <br /> Fixtures Required - Secondary Water Closets Lavatories <br /> Staff* 1:1-15 1:1-15 <br /> Male Occupants 1/40 occupants 1/40 occupants <br /> Female Occupants 1/30 occupants 1/40 occupants <br /> 2. Existing Fixtures Available: Water Closets Lavatories <br /> Classroom Wing (male) 4 4 <br /> Classroom Wing (female) 5 4 <br /> Classroom Wing (staff) 1 1 <br /> Classroom Wing (unisex) 12 <br /> Block Building (male)** 2 2 <br /> Block Building (female)** 2 2 <br /> Total Available 14 25 <br /> 3. Middle School Occupied Area: <br /> �r Classroom Wing 8,100 s.f. net <br /> Exercise Room Wing 13,900 s.f. net <br /> Total Area 22,000 s.f. net <br /> 4. Middle School Occupant Load: <br /> 22,000 s.f. net(Total Area)/ 50 s.f./occ. =440 occupants <br /> 220 male occupants <br /> 220 female occupants <br /> 5. Fixtures Required: Water Closets Lavatories <br /> Staff(1 1)* 1.0 1.0 <br /> Male Occupants (220) 5.5 5.5 <br /> Female Occupants (220) 7.3 5.5 <br /> Total Required 13.8 (14) 12.0 <br /> 6. CONCLUSION Plumbing fixtures provided in the Middle School Classroom <br /> Wing and adjacent block building satisfy the minimum fixture <br /> requirement for the Classroom and Exercise Room wings as <br /> one school faculty. <br /> (1) unisex restroom, with (1) water closet and (1) lavatory, allowed where staff <br /> occupant load is 15 or less. (IBC/OSSC 2902.3 Exception 1) <br />