FIRE AND SMOKE PROTECTION FEATURES <br /> ferential of 0.01 inch of water(2.49 Pa).The system 6. Noncombustible items that are cast into con- <br /> shall have an F rating/T rating of not less than 1 hour crete building elements and that do not pene- <br /> but not less than the required rating of the floor pen- trate both top and bottom surfaces of the <br /> etrated. element. <br /> Exceptions: 7. The ceiling membrane of 1- and 2-hour fire- <br /> 1. Floor penetrations contained and located resistance-rated horizontal assemblies is per- <br /> within the cavity of a wall above the floor mitted to be interrupted with the double wood <br /> or below the floor do not require a T rating. top plate of a fire-resistance-rated wall assem- <br /> bly,2. Floor penetrations by floor drains, tub provided that all penetrating items <br /> through the double top plates are protected in <br /> drains or shower drains contained and accordance with Section 714.4.1.1.1 or <br /> located within the concealed space of a hor- 714.4.1.1.2. The fire-resistance rating of the <br /> izontal assembly do not require a T rating. wall shall not be less than the rating of the hor- <br /> 714.4.1.2 Membrane penetrations. Penetrations of izontal assembly. <br /> membranes that are part of a horizontal assembly shall 714.4.1.3 Dissimilar materials.Noncombustible pene- <br /> comply with Section 714.4.1.1.1 or 714.4.1.1.2.Where rating items shall not connect to combustible materials <br /> floor/ceiling assemblies are required to have a fire- <br /> beyond the point of firestopping unless it can be dem- <br /> resistance rating, recessed fixtures shall be installed onstrated that the fire-resistance integrity of the hori- <br /> such that the required fire resistance will not be zontal assembly is maintained. <br /> reduced. <br /> 714.4.2 Nonfire-resistance-rated assemblies. Penetra- <br /> Exceptions: tions of nonfire-resistance-rated floor or floor/ceiling <br /> 1. Membrane penetrations by steel, ferrous or assemblies or the ceiling membrane of a nonfire-resis- <br /> copper conduits,pipes,tubes or,vents,or con- tance-rated roof/ceiling assembly shall meet the require- <br /> crete or masonry items where the annular ments of Section 713 or shall comply with Section <br /> space is protected either in accordance with 714.4.2.1 or 714.4.2.2. <br /> Section 714.4.1.1 or to prevent the free pas- 714.4.2.1 Noncombustible penetrating items. Non- <br /> sage of flame and the products of combustion. combustible penetrating items that connect not more <br /> The aggregate area of the openings through <br /> the membrane shall not exceed 100 squaremar' five stories are permitted,provided that the annu- I l j <br /> inches (64 500 tutu') in any 100 square feet lar space is filled to resist the free passage of flame and <br /> the products of combustion with an approved noncom- <br /> (9.3 m2) of ceiling area in assemblies tested bustible material or with a fill, void or cavity material <br /> without penetrations. that is tested and classified for use in through-penetra- <br /> 2. Ceiling membrane penetrations of maximum flan firestop systems. <br /> 2-hour horizontal assemblies by steel electri- <br /> cal boxes that do not exceed 16 square inches connect Penetrating items. Penetrating items that <br /> pro- <br /> (10 323 mm2) in area, provided the aggregate vided t not more than two stories are permitted,area of such penetrations does not exceed 100 that the annular space is filled with an approved <br /> square inches(44 500 mm2)in any 100 square material to resist the free passage of flame and the <br /> feet(9.29 m2)of ceiling area,and the annular products of combustion. <br /> space between the ceiling membrane and the 714.5 Penetrations in smoke barriers. Penetrations in <br /> box does not exceed'/a inch(3.2 mm). smoke barriers shall be protected by an approved through- <br /> 3. Membrane penetrations by electrical boxes of penetration firestop system installed and tested in accordance <br /> any size or type,which have been listed as pats with the requirements of UL 1479 for air leakage. The L rat- <br /> of an opening protective material system for ing of the system measured at 0.30 inch(7.47 Pa)of water in <br /> use in horizontal assemblies and are installed both the ambient temperature and elevated temperature tests, <br /> in accordance with the instructions included in shall not exceed: <br /> the listing. 1. 5.0 cfm per square foot(0.025m3/s•m2)of penetration <br /> 4. Membrane penetrations by listed electrical opening for each through-penetration firestop system; <br /> boxes of any material, provided such boxes or <br /> have been tested for use in fire-resistance- 2. A total cumulative leakage of 50 cfm (0.024m3/s) for <br /> rated assemblies and are installed in accor- any 100 square feet(9.3 m')of wall area,or floor area. <br /> dance with the instructions included in the list- <br /> ing. The annular space between the ceiling <br /> membrane and the box shall not exceed 1/3 SECTION 715 <br /> inch(3.2 ruin)unless listed otherwise. FIRE-RESISTANT JOINT SYSTEMS <br /> 5. The annular space created by the penetration 715.1 General.Joints installed in or between fire-resistance- I. <br /> of a fire sprinkler,provided it is covered by a rated walls, floor or floor/ceiling assemblies and roofs or <br /> metal escutcheon plate. roof/ceiling assemblies shall be protected by an approved <br /> 140 2014 OREGON STRUCTURAL SPECIALTY CODE <br />