Laserfiche WebLink
Page 1 of 2 <br /> Troy Wheeler-Re: Stayton Coop Telephone,Activity#08-09449 <br /> From: "Paul Nees"cpaul.nees@state.or.us> <br /> To: 'Troy Wheeler"<twheeler@co.marion.or.us> <br /> Date: 03/23/2009 4:28 PM <br /> Subject: Re:Stayton Coop Telephone,Activity#08-09499 <br /> Stayton Fire Department and I accepted this as an alternative to not sprinkle communication buildings where it <br /> is separated from the rest of the building by a two hour separation. <br /> Paul A. Nees <br /> Deputy State Fire Marshal <br /> Office of State Fire Marshal <br /> Oregon State Police <br /> 4760 Portland Rd NE <br /> Salem, OR 97305 <br /> Tel - 503 934-8289 <br /> Cell - 503 559-0419 <br /> Fax - 503 373-1825 <br /> paul.nees@state.or.us <br /> Premier Public Safety Services <br /> >>> 'Troy Wheeler" <twheeler@co.marion.or.us> 03/23/2009 3:46 PM >>> <br /> Yes, 620 gallon diesel tank under the generator in a 260 sq. ft. room. <br /> Looks as if he is proposing a 2 hr wall and ceiling, rated door, <br /> thegreater than 30'separation to center of streets, heat detection, UL <br /> isted fuel tank that is doubled walled. <br /> I have attached the information that he has given us on the tank. <br /> Thanks, <br /> Troy Wheeler, Plans Examiner <br /> Marion County Building Inspection <br /> Ph: 503-373-4424 <br /> >>> "Paul Nees" <paul.nees@state.or.us> 03/23/2009 1:18 PM >>> <br /> Was this the alternative to not sprinkler the building with the <br /> generator fuel tank under the generator? <br /> Paul A. Nees <br /> Deputy State Fire Marshal <br /> Office of State Fire Marshal <br /> Oregon State Police <br /> 4760 Portland Rd NE <br /> Salem, OR 97305 <br /> Tel - 503 934-8289 <br /> Cell - 503 559-0419 <br /> Fax- 503 373-1825 <br /> Laul.nees@state.or.us <br /> remier Public Safety Services <br /> file://C:\Documents and Settings\twheeler\Local Settings\Temp\GW}00001.HTM 03/23/2009 <br />