Laserfiche WebLink
8~56 Jeanne Ct., Aumsville <br />April 5, 1994 <br />Page 2 <br /> <br />10. <br /> <br />11. <br /> <br />12. <br /> <br />Bathrooms shall be provided with artificial light and an approved <br />mechanical ventilation system capable of producing a change of air every <br />12 minutes or a window of not less than 3 sq. ft., one-half Of which <br />must be openable. <br /> <br />Fixtures in the bathroom shall be placed as per Figure No. R-207.2. The <br />minimum clearance in front of a water closet is 21". <br /> <br />Provide screened attic vents with a net free area of 1/150 of the attic <br />area (or 1/300 if half is along eaves and the other half in the upper <br />portion). (R-707) <br /> <br />MINIMUM COMPONENT REQUIREMENTS: Walls R-15; Floors R-21; Flat Ceilings <br />R-38; Vaults R-21; Basement Walls R-21; Slab Edge R-10; Duct Insulation <br />R-@. R-values used in this table are nominal, for the insulation only <br />and not for the entire assembly. Window and skylight U-values shall not <br />exceed 0.65 (CL65). DOOr U-values shall not exceed 0.54 (Nominal R-2). <br />The minimum wall component for Path 9 shall be an average solid log or <br />timber wall thickness of 3.5 inches. <br /> <br />Approval as a result of this plan review or an inspection shall not be <br />construed to be an approval of a violation of the provisions of the dwelling <br />code or of other ordinances of the jurisdiction. Reviews or inspections <br />presuming to give authority to violate or cancel the provisions of the <br />dwelling code or of other ordinances of the jurisdiction shall not be valid. <br /> <br />sf <br /> <br />"APPROVED" only when this sheet is attached to plans <br /> <br /> <br />