14357 Keil Rd NE, Aurora <br />January 2, 1992 <br />Page 2 <br /> <br />10. <br /> <br />Heating, cooking, air conditioning and similar service equipment are <br />required to be approved and listed by a nationally recognized testing <br />agency, such as Underwriters Laborateries~ Inc., and to be installed in <br />compliance with the agency*s specifications and recognized safe <br />practices. The installation of ventilation systems is required to be in <br />substantial compliance with the 1990 Mechanical specialty code. <br /> <br />Underground fuel storage shall be in compliance with Article 79 and <br />Division VI of the Uniform Fire Code~ This plan review does not cover <br />Department of Environmental Quality regulations. Design calculations <br />for the tank were not submitted with the application and are not <br />included in this review. <br /> <br />117 <br /> <br />Where a tank may become buoyant due to a rise in the level of the wate~ <br />table, suitable precautions shall be observed to anchor the tank in <br />place. (79.601(c) U.F.C.) <br /> <br />Approval of submitted plans is not an approval of omissions Or oversights by <br />this office or of noncompliance with any applicable regulations of local <br />government. <br /> <br />Local Fire Districts may have additional requirements that affect this <br />project. You are advised to contact the Pire District before you proceed. <br /> <br />If you have any q~estions~ please contact me at 588-5147. <br /> <br />TARNO COLEMAN, P~E. <br />PLAN CHECK ENGINEER <br /> <br />DONALD W<KDDLEY <br />BUILDING OFFICIAL <br /> <br />TC/DW <br /> <br />cc: file <br /> <br /> <br />