General and Specialty Electrical Contractors <br /> <br />7-06-98 <br /> <br />Marshall <br />Marion County Electrical inspection dept. <br /> <br />Re: ISBERG R.V. PARK North Extension <br /> <br />Marshall, <br /> <br />I have decided to run all of the feeders with the same size conductors and pipe size. <br />The following list shows the projected Voltage Drop at each pedestal, these <br />calculations are based on each RV drawing 50 Amps Simultaneously. The RV <br />pedestals will be pedestal mounted Loop feed type, equiped with (1) 20 amp GFI <br />outlet, (1) 30 Amp 120 Volt receptacle, and (1) 50 Amp 240 Volt receptacle. <br /> <br />RV Pedestal # Typical Max. Load (amps) @ 240 Volts V.D. % V.D. <br />25 100 0.7 0.3 <br />26 50 0.7 0.3 <br />3 150 4.1 1.7 <br />2 100 3.7 1.5 <br />1 50 2.3 1.0 <br />15 200 4.3 1.8 <br />16 150 4.6 1.9 <br />17 100 3.8 1.6 <br />18 50 2.3 1.0 <br />46 200 4.9 2.0 <br />47 150 4.4 1.8 <br />20 1 O0 4.0 1.7 <br />19 50 2.3 1.0 <br />42 200 3.1 1.3 <br />43 150 3,O 1,2 <br />44 1 O0 2.5 1.0 <br />45 5O 1.5 O.6 <br />41 200 4.0 1.7 <br />40 150 3.7 1.5 <br />39 100 2.9 1.2 <br /> <br />13765 S.E. 282nd Lane · Boring, OR 97009 ° Phone: (503)663-2111 · Fax: (503)663-2906 · CCB# 89153 <br /> <br /> <br />