Laserfiche WebLink
TFP370 <br /> Page 3 of 12 <br /> L Technical (4)`Valve Trim For protection areas not maintained <br /> DV-5 Double Interlock Electric/Electric below 32°F(0°C),a standard air supply <br /> Data Preaction Trim must be used. This without air dryer may be utilized and <br /> component is described in TFP1465. there must be provision for low drains <br /> Approvals to be drained twice a year when the <br /> pp (Sr Quick Opening Device ambient temperature is in excess of <br /> The TYCO QUELL Preaction and Dry Model QRS Electronic Accelerator 32°F(ot) <br /> Systems Components 1 through 6, must be utilized. This component is <br /> described in the next section, are UL described in TFP1100. (8)Fire Detection(Preaction Only) <br /> Listed and FM Approved.The QUELL The fire detection utilized must be <br /> System Component 6(Releasing Panel) (6)*Releasing Panel selected so that it will operate before <br /> is also CE Approved. Potter Electric Series PFC-4410-RC the automatic sprinklers. (The fire <br /> QUELL Systems are intended to (PFC-4410A-RC for Canada)Releasing detection must be compatible with the <br /> mPanel must be utilized.This component Potter Electric Series PFC-4410-RC <br /> be submitted via "Equivalency" as <br /> defined NFPA 13 consequently,the Is described in Potter Manual Releasing Panel. Where acceptable <br /> hydraulic design and water delivery N5403550. to the authority having jurisdiction,the <br /> criteria provided in Tables A,B,and C (7)Automatic Air(Nitrogen)Supply dry contacts of a separate fire detection <br /> are subject to approval by the authority For protection areas maintained below releasing panel may be used to initiate <br /> having jurisdiction and may differ from 32°F (0°C), the air (nitrogen) supply Zone 1 of the PFC-4410-RC shown in <br /> NFPA 13. For FM insured projects, must be provided in accordance with Figure 2.) <br /> consult FM Global. the 2010 Edition of NFPA 13, Section 135°F (57°C) or 155°F (68°C) Linear <br /> Maximum WorkingWater Pressure 7.9.2.4. Heat Detection(LHD)is recommended. <br /> LHD has been verified during full scale <br /> 175 psi(12,1 bar) ' • When Installing per 7.9.2.4(1), the fire testing to meet the fire detection <br /> piping arrangement must be in actor- requirements for QUELL Preaction <br /> Allowable System dance with Figure A 7.9.2.4(i.e.,inclu- Systems. <br /> Air Pressure Range sive of an air dryer and coalescer <br /> 10 to 65 psi(0,69 to 4,5 bar) filter to provide a higher degree of (9)Pipe and Fittings <br /> (See Table D "Nominal Pressure" preventing the formation of ice plugs). Pipe must be internally galvanized <br /> column for allowable system pressure • When installing per 7.9.2.4(2), the or equivalent and of a type material <br /> settings. Also refer to Model ORS use of an air drying unit is required. acceptable per NFPA 13 for preaction <br /> Electronic Accelerator data sheet In the Americas, the General or dry systems. <br /> TFP1100.) Air Products Dry Air Pac Model Exception:Pipe may be black only for <br /> 4 Maximum System Volume DAP500, DAP1000, or DAP2000 is a QUELL Preaction System and only <br /> recommended. This component is when all three of the following criteria <br /> 4200 gallons(15900 liters) described in General Air Products are met: <br /> DAP-Instruction Manual-011606. • all system piping is in areas main- <br /> NONCE Note:When utilizing a Listed Dry Air tained below 32°F(0°C) <br /> SpnnkFDT-Q Fluid Delivery Calculation Pac supplying multiple risers,a sepa- <br /> Program must be applied to assure rate Air Maintenance Device(AMD-1) For systems where piping passes <br /> desired water delivery time. must be utilized for each riser. Any through areas which are below <br /> factory-supplied Air Maintenance 32°F(0°C), as well as areas above <br /> Device equipped with the Dry Air Pac 32°F (0°C), the black pipe excep- <br /> tion tion cannot be utilized for any of the <br /> requires that the Bypass be main- <br /> system piping within the freezer/ <br /> Components tamed fully opened to supply air to cooler walls. <br /> each riser AMD-1 device. Each riser <br /> (& Data Sheet AMD-1 can then be adjusted individ- • a listed air compressor/dryer package <br /> ually for the designed air pressure is provided per NFPA 13, 7.9.2.4(2) <br /> Reference) for each system. It only one riser is or a compressed nitrogen supply <br /> being supplied by the Dry Air Pac, is provided per NFPA 13, 7.9.2.4(3), <br /> (1)"Automatic Sprinklers the factory-supplied Air Maintenance refer to Component 7 <br /> Device on the Dry Air Pac is sufficient <br /> Ultra K17 (TY7103)Upright Sprinklers • the system is to be trip tested in a <br /> (Ref. Figure 4) with a 286°F (141°C) for air maintenance of the single riser, manner that does not introduce mois- <br /> temperature rating must be utilized. • When installing per 7.9.2.4(3), the tare into the system piping <br /> This component is described in use of the Model AMD-3 Nitrogen (The 2011 Edition of NFPA 25,Section <br /> TFP331. Maintenance Device is recom- 13.4.3.2.5 requires that proac- <br /> `Automatic Control Valve mantled. This component is Lion valves protecting freezers (Le., <br /> 121 described in TFP1241. below32°F[0°C])shall be trip tested <br /> DV-5 Deluge Valve(automatic control <br /> valve) must be utilized for both "components t,z.s.4,5,and 6 have thepSnselect- inamaeint that does not introduce <br /> preaction and dry systems. This ad based en t t ability to meet the performance this in re into the system piping. With <br /> component is described in TFP1305. requirements of the Q System and in some this in mind, the riser for the QUELL <br /> cases the O compatibility of cenain components, System (Figure 1) is provided with <br /> (3)"Riser Check Valve e.g..the Model ORS Electronic Accelerator with a System Shut-Off Valve so that <br /> the Series Pfcalla-Rc Releaa'n Panel,II MP <br /> • Model CV-1 FR Riser Check Valve musttrip tests can be discharged to the <br /> not aware of alternative components that meet <br /> . be utilized for both preaction and dry me QUELL System performance requirements. System Main Drain Valve instead of <br /> L systems.This component is described Accordingly,at INS there is no assurance that the system piping.) <br /> in TFP950. QUELL systemss wilt function as intended il the in- <br /> dicated components are notp used. It is possible <br /> that functional alternativesestto these components <br /> will be developed and tested in the future <br />