1 TECHNICAL CHAPTER 6:PLUMBING ELEMENTS AND FACILITES <br /> 608.3.3 Alternate Roll-In Type Shower Compartments. In alternate roll-in type shower <br /> compartments, grab bars shall be provided on the back wall and the side wall farthest from the <br /> compartment entry. Grab bars shall not be provided above the seat. Grab bars shall be installed 6 <br /> inches (150 mm) maximum from adjacent walls. <br /> 6 max 6 max <br /> 150 \, <br /> ... ... <br /> I I badcwall <br /> a side <br /> vra� L wall <br /> m <br /> front wall <br /> Figure 608.3.3 <br /> Grab Bars for Alternate Roll-In Type Showers <br /> 6.08 4 Seats! A folding or non-folding seat shall be provided in transfer type shower compartments. A <br /> folding seat shall be provided in roll-in type showers required in transient lodging guest rooms with -- <br /> mobility features complying with 806.2. Seats shall comply with 610. <br /> EXCEPTION: In residential dwelling units, sears shall not be required in transfer type shower <br /> compartments provided that reinforcement has been installed in walls so as to permit the installation <br /> of seats complying with 608.4. <br /> �Ir 608.5 Controls. Controls,faucets, and shower spray units shall comply with 309.4. <br /> 608.5.1 Transfer Type Shower Compartments. In transfer type shower compartments, the <br /> controls, faucets, and shower spray unit shall be installed on the side wall opposite the seat 38 • <br /> inches (965 mm) minimum and 48 inches (1220 mm)maximum above the shower floor and shall be <br /> located on the control wall 15 inches (380 mm) maximum from the centerline of the seat toward the <br /> shower opening. <br /> l� <br /> side well <br /> G 15 max <br /> m' <br /> { / <br /> I <br /> xl <br /> 0m m~ <br /> I tYr <br /> Figure 608.5.1 <br /> Transfer Type Shower Compartment Control Location <br /> hir 178 -2010 Standards:Titles II and III Department of Justice <br />