Laserfiche WebLink
reservoir's location at an elevation well above any building on the property, it is a <br /> gravity-feed water system. BHS has two primary water pumps to deliver potable water to <br /> the reservoir, with a third backup pump available should one of the primaries fail. If one <br /> or more Lodge sprinkler heads is triggered,up to 92,363 gallons of water will be released <br /> to a dedicated pipe that connects the reservoir to the sprinkler system. The system <br /> pressure is 43.3 psi,well above the 40 psi required to charge the system. <br /> 7) State the differences in your design and NFPA 22 requirements <br /> Please see explanations 1 —6 above. <br /> L <br />