Laserfiche WebLink
S ATE ,tA, S NOTICE OF PLAN REVIEW <br /> <br />E~untv ~,~:~rio~ ' oanc~ '~' Ccitt ~-N Sound Value ~2'/~0C) Pa F~e <br />Arch./Engr' ~o~1~ Or&b~kov Ne~ Bldg,~ Addition~.TAlteratio~ Da~o Auce~ved <br /> <br />~ner same __ Address same ~te Reviewed 12/18/85 <br /> <br />Stories I Area i ~00~ BO Attic 8 / none, Fire Walls' no~eExits~ ] / 3 ft. <br /> <br />St~trs mo~e no reft. Shafts ~ ~rtnklers ,~ / -- ~n.Alarm non~.p, no~e -& <br /> T glOS'~ CIOS~ ~00~0 ye~ area covered ~nfT ~g~ <br />Ext, ~,,~ -~t,Det. ~On~ . none Floor ~ ~ Ceiling gY~ Roof , shake~tr,Members <br /> class no, ~ ~'~ %'~ovd. N/~ Fuel ..... <br />Wall Cover ~0~ gYP Htr.~,Encl. N/~ Ty~ Flue Type Htg. Sy~t~ N/S <br /> ex~. <br />The submitted plan~ have been reviewed for conformity with fire protection statutes and regulations of Oregon admlnist <br />tered by this office. The following provision~ mutt ~-) incorporated into the project to meet current fire protection <br />regulations. ~oval of submitted plans is not a~ ~roval of omissions or overstqhts by this office or of <br /> <br /> RE~RKS: <br /> <br /> l} Yhls lsa Fire & gf~e 8a~ety Plan ~evlew oove~lng the oonstruetlon oF bhe above <br /> addition bo the exl~ting building, Thl~ ~evle~ ls ~o~ oompllanee W~th the Fl~e & lifo ~aFety <br /> provisions oF the Oregon State Strootural Speeialky Code and ~iPe and llFe safety regulabion~ <br /> 83 edltlon. <br /> <br />2) This plan review covers a 1,003 sq. ft. addition to a ;4,203 sq. ft. existing building. <br /> <br />3) A firefighting water supply is required Within 500'ft. of the building that is capable of <br />producing 500 gallons per minute for each 5,000 sq. ft, of floor area within the building up <br />to a maximum of 500 GPM for 30 minutes or provide a 5,000 to 15,000 gallon reserve water <br />%~upply as required by ORS 479.200. <br /> <br />4) All insulation materials including facings, such as vapor barriers or breather papers, <br />installed within floor-ceiling assemblies, roof-ceiling assemblies, walls, crawl spaces, or <br />attics shall have a fiasco-spread rating not to exceed 25 and a smoke density not to exceed <br />450 when tested in accordance with UBC Standard No. 42-1. <br />Except when such materials are ~nsta!led in concealed spaces oF Types III, IV, and V <br />Construction, the flame-spread and smoke-developed limitations do not apply to facings, pro- <br /> installed in substantial contact with the unexposed surf@ce of ti~e <br />ceiling, floor or walI finish'~'' Ref. C~de]'~'~. 17~3. <br /> <br />5) Exit signs shall be provided at every required exit doorway and wherever otherwise <br />required to clearly indicate the direction of egressi An exit sign with letters having a <br />principal stroke not less than three quarters of an inch i~ width and at least six inches <br />high ehall be provided. Tile building official may authorize the omission of exit signs at <br />main exterior doors which are obviously and oiearly identifiable as exits: Ref. Code, Sec. <br />3314. <br /> <br />6) Exit doors shall be openable from the inside without the use of a key or any special <br />knowledge or effort. Manually operated edge or surfac~ bolts are prohibited: Ref. Code, <br />Sec. 3304(c). <br /> <br />7) Change in floor level at door: there shall be a floor or landing on each side of a door: <br />llef. Code, Sec. 3304(h). <br /> <br />8) Curtains, drapes and similar furnishings are to be noncombustible or rendered and main- <br />tained flameproof: Ref. Code, Sec. 4a05. <br /> <br />9) The roof covering material is required to be fire retardant: Ref. Code, Sec. 3202B. <br /> <br />10) The plans for the above-indicated addition are acceptable as submitted subject to the <br />items noted above and the approval of the authority having jurisdiction. <br /> <br />opies to: <br /> <br /> Done Ray <br /> Examined By: <br />Applicant, File. Dep,S~M. SFM, Owner~pt~,, Fire Oept,, Elec.. Arch,/Enur . Plbg. <br /> <br /> <br />